|
|
Controllers Configuration |
Controllers provide audiovisual feedback on the access decision. Typically, a red/green light (LED) indicator on the reader informs the cardholder that the door is unlocked or that access has been denied. A local door alarm can be installed to provide an audible warning if the door is forced open or remains open after an access.
The controller
definition tells the system how a controller is being used and what devices
are associated with it: (doors, input zones, relays and output devices).
| Type | Door(s) | Relays | Input Zones | Auxiliary Outputs |
| KT-100 | 1 | 4 | 4 | 2 |
| KT-200 | 2 | 2 | 16 | 4 |
| KT-300 | 2 | 2 | 8 | 4 |
| KT-400 | 4 | 4 | 16 | 16 |
| KT-1 | 1 | 2 | 5 | 5 |
1 -
2 -
3 -
4 -
5 -
•
•
6 -

| Reader Types | KT-100 | KT-200 | KT-300 | KT-400/KT-1 |
|---|---|---|---|---|
| ABA with Type CNPID Cards | Yes | Yes | Yes | |
| BC-201 - CF100 | Yes | Yes | Yes | |
| BC-201 Bar code with Polaris Cards | Yes | Yes | Yes | Yes |
| CARDKEY | Yes | Yes | Yes | |
| CASI-RUSCO 26/28-Bit Wiegand | Yes | Yes | Yes | |
| CHECKPOINT Sielox Format | Yes | Yes | Yes | |
| CHUBB | Yes | Yes | Yes | |
| DORADO ABA clock and data | Yes | Yes | Yes | |
| DORADO ABA Wiegand | Yes | Yes | Yes | |
| DORADO EMPI 26-Bit | Yes |
| Yes | |
| DORADO EMPI 34-Bit | Yes | Yes | Yes | |
| FIPS 201 75-bit no expiry date | Yes | |||
| FIPS 201 75-bit with expiry date | Yes | |||
| H10302, 37-Bit | Yes | Yes | Yes | Yes |
| HID CORPORATE 1000 Generic | Yes | Yes | Yes | Yes |
| HID iClass 37-Bit No Party | Yes | |||
| HID KSF (Kantech Secure Format) | Yes | Yes | Yes | Yes |
| HUGHES 36-Bit - CF104 | Yes | Yes | Yes | |
| INDALA old 27-Bit Format | Yes | Yes | Yes | |
| INTERCON | Yes | Yes | Yes | |
| ioProx Dual Driver (26-Bit and XSF) | Yes | Yes | Yes | Yes |
| ioProx Kantech 26-Bit Wiegand | Yes | Yes | Yes | Yes |
| ioProx Kantech XSF Format | Yes | Yes | Yes | Yes |
| ioProx UK 31-Bit Wiegand | Yes | |||
| KRONOS Card with Bar Code Reader | Yes | Yes | Yes | |
| Mifare 32-Bit CSN | Yes | Yes | Yes | Yes |
| Mifare 34-Bit AID 517A | Yes | Yes | Yes | |
| Mirage 135 | Yes | Yes | Yes | |
| NCS | Yes | Yes | Yes | |
| Northern 32-Bit with NR1 Reader | Yes | Yes | Yes | |
| Northern 34-Bit with Hughes Reader | Yes | Yes | Yes | |
| Paramount Farm 32-Bit Wiegand | Yes | Yes | Yes | Yes |
| Polaris 1 - CF101 | Yes | Yes | Yes | |
| Polaris 1 with 10-Digit Cards | Yes | Yes | Yes | |
| Polaris 1 with 16-Digit Cards | Yes | Yes | Yes | |
| Polaris 1 with Polaris Cards | Yes | Yes | Yes | Yes |
| Polaris 2 ABA with 10-Digit Cards | Yes | Yes | Yes | |
| Polaris 2 ABA with 16-Digit Cards | Yes | Yes | Yes | |
| Polaris 2 ABA with Polaris Cards | Yes | Yes | Yes | Yes |
| Polaris 2KP ABA with 10-Digit Cards | Yes | Yes | Yes | |
| Polaris 2KP ABA with 16-Digit Cards | Yes | Yes | Yes | |
| Polaris 2KP ABA with Polaris Cards | Yes | Yes | Yes | Yes |
| Polaris 32/35/37 CHRS - CF103 | Yes | Yes | Yes | |
| RBH 50-Bit Card Driver | Yes | |||
| SCHLAGE 1030 and 1040 Card Format | Yes | Yes | Yes | |
| Sensor 26-Bit Wiegand Standard | Yes | Yes | Yes | Yes |
| Sensor 34-Bit Wiegand | Yes | Yes | Yes | Yes |
| SFT-R50 26-Bit | Yes | Yes | Yes | |
| Shadow PROX | Yes | Yes | Yes | Yes |
| Siteguard Format | Yes | Yes | Yes | |
| Wiegand 26/28-Bit - CF102 | Yes | Yes | Yes | |
| WLS Wireless 26-Bit | Yes | Yes | Yes | |
| WLS Wireless Shadow Prox and HID | Yes | Yes | Yes |
7 -
| Keypad Types | KT-100 | KT-200 | KT-300 | KT-400/KT-1 |
| KP-1003H | Yes | Yes | Yes | |
|---|---|---|---|---|
| KP-500, KP-2000, KP-2500, KP-3000 | Yes | Yes | Yes | |
| ioProx with Integrated Keypad (8-Bit Burst) | Yes | Yes | Yes | Yes |
| POL-2KP - 5-Digit Integrated Keypad | Yes | Yes | Yes | Yes |
8 -
9 - Select the Vital LED mode (for KT-1 only). Please refer to KT-1 Installation manual D29008966 for details.
10 - Select between On demand and Always on for the Status LED (for KT-1 only). Please refer to KT-1 Installation manual D29008966 for details.
11 -
1 -
2 -
3 - For KT-400 only:
• To configure SPI modules, please refer to Expansion Modules Setup.
• To configure the elevator floor associations, please refer to Defining the KT-400 Elevator Floor Associations.
4 - For KT-300 only:
• To configure Combus Modules, please refer to KT-300 Combus Modules.
• To configure the elevator floor associations, please refer to Defining the KT-300 Elevator Floor Associations.
5 - For KT-200 only:
• To configure KT-200 Auxiliary devices , please refer to Configuring KT-200 Auxiliary Devices.
• To define REB-8 relays, please refer to Defining REB-8 Relays.
• To configure REB-8 elevator controllers, please refer to Programming REB-8 Elevator Controllers.
• To configure KT-2252 elevator controllers, please refer to Programming KT-2252 Elevator Controllers.
6 -
7 -
8 -
9 -
button to select a relay or a group of relays (not available for KT-100).
The Option tab enables operators to configure such features as:
•
•
•
1 -
2 -
•
•
3 -
4 -
•
•
•
•
5 -
6 -
7 -
8 -
9 -
button to select the
relay or relay group that will be activated when the number is reached.
1 - Select a schedule for the Power supervision (not available for KT-1).
2 - Select a schedule for the Tamper switch (not available for KT-100 and KT-300).
Please refer to Schedules Definition for more details about schedule configuration.
1 -
2 -
•
•
•
The Elevator tab allows you to specify which auxiliary devices are used with the KT-200 for elevator control and how they are used. Depending on the expansion board installed and on the option checked, the Elevator window displays the REB-8 Installed or KT-2252 Installed section.
1 -
2 -
3 -
4 -
•
•
The Inputs column refers to the KT-2252 terminals. When floors have been defined (in the Floor menu), the Floorscolumn contains the floors that are associated with the inputs.
• In the KT-2252 installed section, specify the number of KT-2252 installed. The options are cumulative. If for example the KT-2252 #3 option is checked, KT-2252 #1 & 2 have to be checked as well. The following table summarizes how KT-2252 elevator controllers are used:
| Number of Cabs | Number of Floors | Number of KT-2252 |
| 1 | 8 | 1 |
|---|---|---|
| 1 | 16 | 1 |
| 1 | 32 | 1 |
| 1 | 64 | 2 |
| 2 | 8 | 1 |
| 2 | 16 | 1 |
| 2 | 32 | 2 |
| 2 | 64 | 4 |
5 -
The Inputs column refers to the KT-2252 terminals. When floors have been defined (in the Floor menu), the Floors column contains the floors associated with the inputs.
REB-8 relay expansion boards may be used as a cost-efficient alternative for elevator control. With a REB-8 expansion board added to a KT-200, the software may control up to two elevator cabs per controller.
1 -
2 -
3 - Specify the number of REB-8 that are installed on the controller. The selection is cumulative. For example, if four REB-8 are installed, the first three checkboxes have to be checked also. The following table summarizes how REB-8 are assigned to floors and to elevator cabs.
| Number of REB-8 | Number of Floors | Number of Cabs |
| 1 | 1 to 8 | Cab 1 |
|---|---|---|
| 2 | 9 to 16 | Cab 1 |
| 3 | 1 to 8 | Cab 2 |
| 4 | 9 to 16 | Cab 2 |
Note...
4 - In the Floors column, select the floors associated with REB-8 controller terminals. For details on floor definition and door group definition, see Doors Configuration.
When REB-8 are used as relays, you need to specify how many relays are installed on the KT-200. The controller can handle a maximum of 16 accessible relays and already provides 2 on-board relays.
1 -
2 -
3 -
4 -
5 -
The Elevator tab displays only when Combus modules have been defined as elevators under the KT-300 tab.
1 -
2 -
3 -
To define floors, please refer to Floor Definition.
The KT-400 support expansion modules through its SPI expansion port. The SPI port is a 6-conductor cable bus to which several expansion modules are daisy-chained to add inputs, outputs and relays.
Three expansion module types are available:
•
•
•
The following table summarizes the options associated with each module:
| Expansion Module | Options |
| KT-MOD-INP16 | Controller inputs (up to 256) and/or elevator inputs (up to 64 per elevator door) |
|---|---|
| KT-MOD-OUT16 | Outputs relays (up to 256) and/or elevator outputs (up to 64 per elevator door) |
| KT-MOD-REL8 (Note) | Relays (up to 256) and/or elevator outputs (up to 64 per elevator door) |
1 -
| If you want to | then go to |
| configure an input module KT-MOD-INP16 | Step 2. |
|---|---|
| configure an output module KT-MOD-OUT16 | Step 5. |
| configure an output module KT-MOD-REL8 | Step 6. |
| modify an existing expansion module configuration | Step 7. |
2 -
3 -
4 - Selection of the inputs numbers can be done in two ways: using the drop-down menu or the Extended selection box. Right-click on the inputs menu selection to view the Extended selection box, see Using the Extended Selection Box
5 -
6 -
Warning: There are already 4 relays available on the KT-400. Make sure to check the relay number assignments to prevent redundancy unless it has been planned on purpose.
7 -
8 -
For more information, Connection Configuration.
1 - C
2 -
3 -
4 -
5 -
6 -
7 -
The Elevator tab displays only when expansion modules have been defined as inputs or outputs for elevators under the KT-400 tab.
For KT-400 controller, it is possible to choose up to four patterns to define door and floor numbers that will be associated with each pattern. By default, pattern 1 specifies all door numbers.
1 -
2 -
3 -
4 -
5 -
To define floors, please refer to Floor Definition.
The enrolment button is used to send an “enroll me” request to EntraPass with the controller status which includes:
• IP address
• How it is powered (PoE or 12 VDC)
• Full Status
1 - The installers press the enrollment button.
2 - The controller then sends information for a period of 10 minutes at 30 seconds intervals.
3 - Once the 10 minutes delay is expired, the controller stops sending information.
For the enrollment process to be allowed for a given operator, it must first be enabled in System/Security Level/Devices/Connection/Enrollment.
When an enrollment request is received, a circled digit will be displayed at the bottom right side of the workstation main window. The digit indicates the number of unassigned controllers. When there is only one unassigned controller, double-click on the circle to open the Enrollment Wizard. Follow instructions on the screen. You can also do a right-click on it to display a contextual menu that contains the following options:
• Define: Display the Enrollment Wizard.
• Full Status: Displays the full status window. Provide a pop-up box with the IP address, how it is powered (IP or 12 VDC) and the full status information.
• Delete: Remove the selected controller from the list.
• Assign to an account.
When EntraPass receives data from the KT-1 enrollment process it adds the controller to the controllers unassigned list. the "Controller was added to the unassigned list” event is then generated with the following parameters:
• Gateway description
• MAC Address
• Device type
The unassigned controllers list displays:
• Date and time (when it was added to the list) of the gateway
• Controller model
• MAC Address
• Serial Number
• Broadcast received IP address
The unassigned controller list can have a limited number of 100 entries.
When a controller is disconnected from the server, the controller buffer starts collecting the controller’s events. When the buffer is full, it transfers the oldest events in a secondary buffer (50 to 100 bytes) that always contain 50 events. When the communication is restored, the system then starts sending messages to the Desktop Message List to indicate that the buffer is full and that events are being deleted from the buffer.
• The controller will delete messages in FIFO order (First In, First Out). The oldest message will therefore be deleted first.
• When the controller is reconnected to the server, the controller events will be sent to the Message list all at once, in the following order: events in the controller’s secondary event buffer; a single Event Buffer Overflow will display, followed by the list of events generated while the controller was disconnected from the server.
For more details about the Comment entry box, please refer to Comment Field.
Note